ATP in practice: classes, the K coefficient and test intervals

How to read an ATP marking such as FRC, how insulated and refrigerated bodies differ, and when the certificate must be renewed.

Trucklo editorial team Updated: · 5 min read
ATP in practice: classes, the K coefficient and test intervals

W skrócie

  • The ATP Agreement sets the requirements for vehicles carrying perishable foodstuffs internationally.
  • The marking is made of letters: equipment type (I, R, F, C), insulation (N or R) and temperature class (A–F).
  • FRC is a mechanically refrigerated body with heavy insulation, class C: any set point from +12 °C to −20 °C.
  • The first certificate is issued for up to 6 years, then extended after a test under the rules of the country of registration.
  • K ≤ 0.40 W/m²K, heavy insulation (R)
  • K ≤ 0.70 W/m²K, normal insulation (N)
  • 6 years validity of the first certificate

How to read an ATP marking

A marking such as FRC is a code. The first letter gives the equipment type, the second the insulation, the third the temperature class. A fourth letter X, where present, means a removable or non-independent thermal appliance.

PositionLetterMeaning
1IInsulated (no thermal appliance)
1RRefrigerated without a unit, e.g. ice, eutectic plates
1FMechanically refrigerated
1CHeated
2NNormal insulation, K ≤ 0.70 W/m²K
2RHeavy insulation, K ≤ 0.40 W/m²K
3A–FTemperature class
4XRemovable or non-independent appliance (optional)

Classes for mechanically refrigerated bodies

For mechanically refrigerated bodies (first letter F), classes A, B and C allow any set point within the range. Classes D, E and F hold a temperature no higher than a limit. Classes B, C, E and F require heavy insulation: K no higher than 0.40 W/m²K.

ClassInside temperatureInsulation
AAny from +12 °C to 0 °CN or R
BAny from +12 °C to −10 °CR
CAny from +12 °C to −20 °CR
DNo higher than 0 °CN or R
ENo higher than −10 °CR
FNo higher than −20 °CR

Refrigeration unit and ATP plate on a refrigerated body

Refrigeration unit and ATP plate on a refrigerated body

The K coefficient

K is the overall heat transfer coefficient of the body walls, in W/m²K. The lower it is, the better the insulation. Normal insulation (N) is K ≤ 0.70; heavy insulation (R) is K ≤ 0.40. Panel thickness, thermal bridges and the number of doors all affect K.

Certificate validity and tests

An ATP certificate for a new vehicle is issued for up to 6 years. It is then extended after a test at an approved station. Procedures differ by country: in the UK the vehicle is retested every 3 years, while France tests at 6 and 9 years with full requalification at 12 years.

What to tell the body builder

  • The target ATP class, e.g. FRC or FRA.
  • Products and temperatures, including multi-temperature loads.
  • Whether the vehicle will run internationally.
  • Number and position of doors, since they affect K.
  • Who arranges the test and collects the certificate.

Frequently asked questions

What does FRC mean on a reefer?

F: mechanically refrigerated, R: heavy insulation (K ≤ 0.40 W/m²K), C: class C, any set point from +12 °C to −20 °C.

What is the K coefficient?

The heat transfer coefficient of the body walls in W/m²K. Normal insulation: K ≤ 0.70; heavy: K ≤ 0.40.

How long is an ATP certificate valid?

The first certificate for a new vehicle: up to 6 years. It is then extended after a test under national rules.

Sources

  1. UNECE: ATP Agreement, Annex 1 (treaty text)
  2. UNECE WP.11: ATP classes A–F, mechanically refrigerated equipment
  3. Cemafroid: ATP marking and certificate lifecycle
  4. GOV.UK: ATP rules on carrying perishable foodstuffs